INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
RSA BOILERS
For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide
Boiler Model Number and Serial Number as shown on Rating Label.
Boiler Model Number Boiler Serial Number Installation Date
_RSA _ _ _ _ _ _ _ _ 6 _ _ _ _ _ _ _
Heating Contractor Phone Number
Address
8143508R3-10/99
Vue de la page 0
1 2 3 4 5 6 ... 47 48

Résumé du contenu

Page 1 - RSA BOILERS

1Price - $3.00INSTALLATION, OPERATING ANDSERVICE INSTRUCTIONS FORRSA BOILERSFor service or repairs to boiler, call your heating contractor. When seek

Page 2

10Figure 5: Burner Mounting2. Bend jacket according to Figure 6. Starting fromthe front, wrap the jacket around the boiler. Makesure that return pi

Page 3

11Figure 6: RSA Jacket Assembly

Page 4

12III. Water Piping and Trim A. Design a piping system and install boiler which willprevent oxygen contamination of boiler water andfrequent water ad

Page 5 - Tables of Contents

13Figure 7: Recommended Piping for Combination Heating and Cooling (Refrigeration) SystemB. Install Pressure Relief Valve. See Figures 8 and 9.Press

Page 6 - In. (dia.) x Ft

14Figure 8: Recommended Boiler Piping for Circulator Zoned Heating Systems

Page 7 - I. Pre-Installation

15Figure 9: Boiler Piping for Zone Valve Zoned Heating Systems

Page 8

162. TEMPERING OF HOT WATER — Installation ofan automatic mixing valve will lengthen thedelivery of the available hot water by mixing somecold water w

Page 9 - A. REMOVAL OF BOILER

17Figure 11: Schematic Tankless Heater PipingTable 1: Tankless Heater RatingsBoiler ModelSTD. #7524 OPT. #7530GPM PSID GPM PSIDRSA170 3¾ 25½ 4 26½RS

Page 10

18IV. VentingA. General Guidelines.1. Vent system installation must be in accordance withthese instructions and applicable provisions of localbuildin

Page 11

19Figure 12: Recommended Smokepipe Arrangement and Chimney RequirementsFigure 13: Draft Regulator Locations

Page 12 - III. Water Piping and Trim

2The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels,or to important information

Page 13

20A. General1. Install wiring and electrically ground boiler inaccordance with requirements of the authorityhaving jurisdiction, or in absence of such

Page 14

21Figure 14: “RSAL” Wiring Less Tankless, Single CirculatorFigure 15: “RSAT” or “RSAR” Wiring with Tankless, Single Circulator

Page 15

22Figure 16: Circulator Zoned Wiring for Honeywell R8888

Page 16

23Figure 17: Zone Valve Zoned Wiring for R8889

Page 17 - GPM PSID GPM PSID

24Figure 18: Different Manufacturer’s Zone Valve Connections to Honeywell R8889NOTICEThe Honeywell R8889 Control is available in two three (3) zone m

Page 18 - IV. Venting

25NOTICEThe Burnham EC5000 Control includes a water temperature sensor. Mount this sensor to thesystem supply piping.8. Burnham EC5000 Circulator Zon

Page 19

26Figure 19: Circulator Zoning with EC5000 Wiring Schematic

Page 20 - V. Electrical

27Figure 20: Zone Valve Zoned with EC5000 Wiring Schematic

Page 21

28A. General.1. Use flexible oil line(s) so that burner can beremoved without disconnecting the oil supply.2. A supply line fuel oil filter is recomme

Page 22

29C. Two-Pipe Oil Lines1. For two-piped systems, where more lift is required,the two-stage fuel unit is recommended. Table 2(single-stage) and Table

Page 23

3DANGERDO NOT store or use gasoline or other flammable vapors or liquids in the vicinity of this or anyother appliance.WARNINGImproper installation, a

Page 24

30VII. System Start-UpA. Verify that the venting, water piping, oil piping, andelectrical system are installed properly. Refer toinstallation instru

Page 25

31SOLID stream without air bubbles for approxi-mately 10 seconds.3. Close vent fitting and burner flame should startimmediately.4. If the burner does

Page 26

32instrumentation to obtain a CO2 of 11.5 to 12.5%with draft of -.02” w.c. in fire box. These settingswill assure a safe and efficient operating cond

Page 27

33extreme case may become a fire hazard.d. AIR LEAKS— Any such leaks should berepaired, as they may cause erratic burning ofthe fuel and in extreme ca

Page 28 - VI. Oil Piping

34a. Simulate flame failure:• Follow the starting procedure to turn on theburner.• Close the hand valve in the oil supply line.• Safety switch should

Page 29 - C. Two-Pipe Oil Lines

35INSTALLATION INSTRUCTIONS FOR SHIELD REQUIRED FOR COMBUSTIBLE FLOORThis shield for combustible floors is intended for use only with the following Bu

Page 30 - VII. System Start-Up

36VIII. Service and CleaningA. General. Inspection service and cleaning should beconducted annually. Turn off electric power and closeoil supply va

Page 31 - L. OTHER ADJUSTMENTS

37IX. Repair PartsAll RSA Repair Parts may be obtained through your local Burnham Wholesale distributor. Should yourequire assistance in locating a

Page 32 - O. HINTS ON COMBUSTION

38NOTE: When ordering parts always give the serial number and model number shown on the boiler. Also provide the name of the part(s) shown below:Figu

Page 33 - P. TEST CONTROLS

39BOILER MODEL'A' 'B'RSA85 12 603350112RSA110 16 603350116RSA125 12 603350212RSA135 16 603350216ITEM NO. QTY. DESCRIPTION PART NO.

Page 34

4WARNINGAppliance materials of construction, products of combustion and the fuel contain alumina, silica,heavy metals, carbon monoxide, nitrogen oxide

Page 35

40Figure 27: RSA170-285 Boiler Repair PartsNOTE: When ordering parts always give the serial number and model number shown on the boiler. Also provid

Page 36 - VIII. Service and Cleaning

41Boiler Model 'A' 'B'RSA170 10 6306332RSA195 13 6306329RSA240 16 6306309RSA285 19 6306310ITEM NO. DESCRIPTION PART NO.1 Jacket To

Page 37 - IX. Repair Parts

42ITEM DESCRIPTION PART NUMBER1 Jacket Top Panel 604350862Jacket Wrap-A-Round Panel, RSA85/110 60435087Jacket Wrap-A-Round Panel, RSA125/135 604350883

Page 38 - REPAIR PARTS

43SERVICE SCHEDULEDATE SERVICE PERFORMED

Page 39 - 'B'

44BECKETT BURNER PARTS LIST FOR RSA SERIES STEEL BOILERSFOR REPLACEMENT OIL BURNER PARTS, CONTACT YOUR WHOLESALER OR THE BURNERMANUFACTURER:R. W. BECK

Page 40

45Ordering Information for Quality Replacement PartsFigure 29: BECKETT AFG MODEL BURNER

Page 41 - for Quantity 6113504

46BECKETT BURNER PARTS LIST FOR RSA SERIES STEEL BOILERSFOR REPLACEMENT OIL BURNER PARTS, CONTACT YOUR WHOLESALER OR THE BURNER MANU-FACTURER:R. W. BE

Page 42 - ITEM DESCRIPTION PART NUMBER

47Ordering Information for Quality Replacement PartsFigure 30: BECKETT AF and SF MODEL BURNERS

Page 44 - 51304 51304 51304 51304

5Tables of ContentsI. Pre-Installation ... 7II. Knockdown Boiler Assembly ... 9III. Water Piping and Tri

Page 45

6Figure 1A: RSA Packaged Boiler (RSA170 / RSA285)BoilerModelNumberBare BoilerAssemblyMinimum Chimney SizesWaterCapacityGallonsApprox.ShippingWeightIn

Page 46

7A. INSPECT SHIPMENT carefully for any signs ofdamage.1. ALL EQUIPMENT is carefully manufactured,inspected and packed. Our responsibility ceasesupon

Page 47

8C. PROVIDE AIR SUPPLY AND VENTILATION toaccommodate proper combustion. If natural ventila-tion is inadequate, provide a screened opening or ductfrom

Page 48

9II. Knock-Down Boiler AssemblyH. INSTALLING THE JACKET1. Before jacket can be secured to boiler assemblytankless heater coil or blank plate must be